Line 3: | Line 3: | ||
https://www.omnicalculator.com/construction/box-fill | https://www.omnicalculator.com/construction/box-fill | ||
*Results - 14 ga 3 wires 1 device - 20 cu in | *Results - 14 ga 3 2-conductor wires 1 device - 20 cu in | ||
*12 ga 3 wires 1 device - 22.5 cu in | *12 ga 3 wires 1 device - 22.5 cu in | ||
*12 ga outlet - 2 2-conductor wires 1 device - 18 cu in | |||
*14 ga outlet - 2 2-conductor wires 1 device - 16 cu in | |||
*3 light switches in a triple box - one 14 ga feed line, 3 separate lines going out - 41.4 |
Latest revision as of 23:42, 8 September 2022
Conductors excluding ground, internal clamps are tabs that hold wires.
https://www.omnicalculator.com/construction/box-fill
- Results - 14 ga 3 2-conductor wires 1 device - 20 cu in
- 12 ga 3 wires 1 device - 22.5 cu in
- 12 ga outlet - 2 2-conductor wires 1 device - 18 cu in
- 14 ga outlet - 2 2-conductor wires 1 device - 16 cu in
- 3 light switches in a triple box - one 14 ga feed line, 3 separate lines going out - 41.4