*'''Aluminum ampacity''' - 1/0 aluminum does 100A at 60C. '''Good chart of wire types and their T resistance [https://wire.buyawg.com/viewitems/all-categories-appendix-allowable-ampacities/sulated-aluminum-or-copperclad-aluminum-conductors]''' | *'''Aluminum ampacity''' - 1/0 aluminum does 100A at 60C. '''Good chart of wire types and their T resistance [https://wire.buyawg.com/viewitems/all-categories-appendix-allowable-ampacities/sulated-aluminum-or-copperclad-aluminum-conductors]''' | ||
*'''Copper Ampacity''' - 2AWG copper is rated for 95A at 60C, 1 AWG is rated for 110 at 60C [https://www.lapptannehill.com/resources/technical-information/ampacity-chart] | *'''Copper Ampacity''' - 2AWG copper is rated for 95A at 60C, 1 AWG is rated for 110 at 60C [https://www.lapptannehill.com/resources/technical-information/ampacity-chart] |
Revision as of 02:52, 22 May 2023
About Service Entrance and SER Cable
- Aluminum ampacity - 1/0 aluminum does 100A at 60C. Good chart of wire types and their T resistance [1]
- Copper Ampacity - 2AWG copper is rated for 95A at 60C, 1 AWG is rated for 110 at 60C [2]
- NM-B house wire is specified for 60C by the NEC, but it can withstand 90C. [3]
- USE-2, RHW-2 and RHH - sunlight, heat, moisture resistant [4]
- Terminations at panels must be rated at 60C - [5] - thus you must specify wire for 60C. For example, if you want 100A, oversize 100A 90C wire to something larger at whose 60C rating you get the required ampacity.
- THHN to subpanel - yes if in conduit - [6]
- Standard practice - individual THHN through conduit or NM-B through stud holes [7]
- Romex or BX wire can be run without conduit - [8]
- Romex goes up to 2 awg [9]
Subpanels
- Since 2008, 4-wire cable is required. [10]
- SER cable is preferred, no conduit needed [11]. XHHW and THHN can be used but require conduit.