*Standard practice - individual THHN through conduit or NM-B through stud holes [https://www.thespruce.com/romex-and-conduit-wiring-in-exposed-locations-1821529] | *Standard practice - individual THHN through conduit or NM-B through stud holes [https://www.thespruce.com/romex-and-conduit-wiring-in-exposed-locations-1821529] | ||
*Romex or BX wire can be run without conduit - [https://www.quora.com/Can-I-run-THHN-wires-through-an-attic-without-a-conduit] | *Romex or BX wire can be run without conduit - [https://www.quora.com/Can-I-run-THHN-wires-through-an-attic-without-a-conduit] | ||
**Romex goes up to 2 awg [https://wesbellwireandcable.com/blog/thhn-vs-romex/#:~:text=Romex%C2%AE%20wire%20is%20available,(AWG)%20to%202%20AWG.] | |||
=Cost= | =Cost= |
Revision as of 23:44, 15 May 2023
About
- NM-B house wire is specified for 60C by the NEC, but it can withstand 90C. [1]
- 2AWG is rated for 95A at 60C, 1 AWG is rated for 110 at 60C [2]
- USE-2, RHW-2 and RHH - sunlight, heat, moisture resistant [3]
- Aluminum ampacity - 1/0 aluminum does 100A at 60C. Good chart of wire types and their T resistance [4]
- Terminations at panels must be rated at 60C - [5] - thus you must specify wire for 60C. For example, if you want 100A, oversize 100A 90C wire to something larger at whose 60C rating you get the required ampacity.
- THHN to subpanel - yes if in conduit - [6]
- Standard practice - individual THHN through conduit or NM-B through stud holes [7]
- Romex or BX wire can be run without conduit - [8]
- Romex goes up to 2 awg [9]