*1/0 aluminum URD is 100A and $2.50/ft [https://www.menards.com/main/electrical/electrical-wire-cable/electrical-service-wire-cable/1-0-1-0-2-al-urd-wire-per-foot/sku3692045/p-1444442902248-c-1525874617506.htm] | *1/0 aluminum URD is 100A and $2.50/ft [https://www.menards.com/main/electrical/electrical-wire-cable/electrical-service-wire-cable/1-0-1-0-2-al-urd-wire-per-foot/sku3692045/p-1444442902248-c-1525874617506.htm] | ||
*2/0 aluminum SER is $4/ft [https://nassaunationalcable.com/products/2-0-2-0-2-0-1-ser?variant=27475844694116¤cy=USD&utm_medium=product_sync&utm_source=google&utm_content=siraj&utm_campaign=siraj&gclid=Cj0KCQjwsIejBhDOARIsANYqkD2eLYP2KtAdbZ-OxBSDF5PEKag2APydjMDCHfaAI4rdHmVbHWr7IM0aAjltEALw_wcB] | *2/0 aluminum SER is $4/ft [https://nassaunationalcable.com/products/2-0-2-0-2-0-1-ser?variant=27475844694116¤cy=USD&utm_medium=product_sync&utm_source=google&utm_content=siraj&utm_campaign=siraj&gclid=Cj0KCQjwsIejBhDOARIsANYqkD2eLYP2KtAdbZ-OxBSDF5PEKag2APydjMDCHfaAI4rdHmVbHWr7IM0aAjltEALw_wcB] | ||
*1/0 aluminum SER is 1.1" OD + $3/ft [https://nassaunationalcable.com/products/1-0-1-0-1-0-2-ser?_pos=2&_sid=f5b6d4b3b&_ss=r]. $4/ft after shipping for 32'. | *{{check}}1/0 aluminum SER is 1.1" OD + $3/ft [https://nassaunationalcable.com/products/1-0-1-0-1-0-2-ser?_pos=2&_sid=f5b6d4b3b&_ss=r]. $4/ft after shipping for 32'. | ||
**$5/ft at Platt [https://www.platt.com/p/0069542/ser-service-entrance-cable-1-0-3-aluminum-1000/662927235561/1a3sergx1000] | **$5/ft at Platt [https://www.platt.com/p/0069542/ser-service-entrance-cable-1-0-3-aluminum-1000/662927235561/1a3sergx1000] |
Revision as of 02:05, 16 May 2023
About
- Aluminum ampacity - 1/0 aluminum does 100A at 60C. Good chart of wire types and their T resistance [1]
- Copper Ampacity - 2AWG copper is rated for 95A at 60C, 1 AWG is rated for 110 at 60C [2]
- NM-B house wire is specified for 60C by the NEC, but it can withstand 90C. [3]
- USE-2, RHW-2 and RHH - sunlight, heat, moisture resistant [4]
- Terminations at panels must be rated at 60C - [5] - thus you must specify wire for 60C. For example, if you want 100A, oversize 100A 90C wire to something larger at whose 60C rating you get the required ampacity.
- THHN to subpanel - yes if in conduit - [6]
- Standard practice - individual THHN through conduit or NM-B through stud holes [7]
- Romex or BX wire can be run without conduit - [8]
- Romex goes up to 2 awg [9]
Subpanels
- Since 2008, 4-wire cable is required. [10]
- SER cable is preferred, no conduit needed [11]. XHHW and THHN can be used but require conduit.