Wire Cost
Jump to navigation
Jump to search
About
- SER cable is preferred, no conduit needed [1]. XHHW and THHN can be used but require conduit.
- NM-B house wire is specified for 60C by the NEC, but it can withstand 90C. [2]
- 2AWG is rated for 95A at 60C, 1 AWG is rated for 110 at 60C [3]
- USE-2, RHW-2 and RHH - sunlight, heat, moisture resistant [4]
- Aluminum ampacity - 1/0 aluminum does 100A at 60C. Good chart of wire types and their T resistance [5]
- Terminations at panels must be rated at 60C - [6] - thus you must specify wire for 60C. For example, if you want 100A, oversize 100A 90C wire to something larger at whose 60C rating you get the required ampacity.
- THHN to subpanel - yes if in conduit - [7]
- Standard practice - individual THHN through conduit or NM-B through stud holes [8]
- Romex or BX wire can be run without conduit - [9]
- Romex goes up to 2 awg [10]