**Good overview doc. Read it from p. 6 on to understand equipment ground, system ground.
**Good overview doc. Read it from p. 6 on to understand equipment ground, system ground.
**Additional issue for PV is that in cloudy conditions, if you get a fault, a breaker may not trip because current is too low. For this reason, extra ground fault protection devices may be required.
**Additional issue for PV is that in cloudy conditions, if you get a fault, a breaker may not trip because current is too low. For this reason, extra ground fault protection devices may be required.
*'''Is earth ground of a PV system connected to DC negative, or to AC neutral?


=More=
=More=

Revision as of 23:19, 15 September 2023

NEC 690 - Covers PV Systems

  • 690.41 - Equipment Grounding Conductor requirements [1]
    • 690.41(B) also requires ground fault protection except if there are no more than 2 strings (PV source circuits [2])
      • Since NEC 2020, ground fault indicator must be readily visible (but not necessarily readily accessible?) [3]
    • 690.45 - size of PV equipment grounding conductors - Table 250.122 + no less than 14 ga.
  • 690.9(A) says that we don't need overcurrent device for PV if the wires can handle short current capacity of PV. But good luck trying to convince a code official.
  • PV Grounding PDF [4]. Although the NEC does not specifically require all equipment to be certified/listed, many local jurisdictions and many AHJs establish requirements that all equipment be certified/listed because they feel unqualified to examine uncertified/unlisted equipment for safety as the NEC requires.
    • Good overview doc. Read it from p. 6 on to understand equipment ground, system ground.
    • Additional issue for PV is that in cloudy conditions, if you get a fault, a breaker may not trip because current is too low. For this reason, extra ground fault protection devices may be required.
  • Is earth ground of a PV system connected to DC negative, or to AC neutral?

More

  • Check.pngSolar PV standards and certifications - [5]. Class II means frames grounded, no system ground.

Pvstandards.png

  • Fire safety and personnel safety are typically tradeoffs? [6]
    • Solidly grounded means neutral is connected to earth electrode. [7]

Equipment Grounding

  • PV panels should follow electrical grounding conductor sizes - [8]
  • Ie, for 30A DC, we need 10 ga ground.
  • PV frames must be connected to PV system equipment grounding conductor [9]
  • After leaving the PV array, the equipment ground must run together with the power wires. [10]

What Size Grounding Conductor on PV Panels?

  • Australia rules - appear to say 6 ga for lightning protection, and 12 ga for frame grounding [11]
  • 6 ga USA if 'subject to damage'?